Product Details:
|
Usage: | Industrial Machinery, Measurement Instrument | Accuracy: | 0.5%FS |
---|---|---|---|
Working Voltage: | 100~240V AC/DC | Power Consumption: | ≤6W |
Working Environment: | 0~50℃ <85%RH | Relay Output: | 3A/250V AC |
Communication: | RS485 | ESD: | IEC/EN61000-4-2 |
Highlight: | LCD Display RS485 Temperature Controller,High Light LCD Display Temperature Controller,250V AC RS485 Temperature Controller |
TP series intelligent digital temperature controller High light LCD display RS485 3A/250V AC 0.5%FS IEC61010-1
1. Features and advantages of TP temperature controller:
a). High light all sight FTN LCD display.
b). Multi input signal and multi dimensions for option.
c). Optional control output:RELAY/SSR/analog.
e). Multi PID algorithms for option, with auto tune function.
2. Model specification and order information:
3. Technical parameter:
Electrical parameter:
Sampling rate | 2 times per second |
Relay capacity | AC 250V/3A Life of rated load>100,000 times |
Power supply | AC/DC 100~240V (85-265V) |
Power consumption | < 6VA |
Environment | Indoor use only, temperature: 0~50℃ no condensation, humidity<85%RH, altitude<2000m |
Storage enenvironment |
-10~60℃,no condensation |
SSR output | DC 24V pulse voltage, load<30mA |
Current output | DC 4~20mA load<500Ω, temperature drift 250PPM |
Communication port | RS485 port Modbus-RTU protocol, max input 30 units |
Insulation impedance | Input, output, power VS meter cover>20MΩ |
ESD | IEC/EN61000-4-2 Contact ±4KV /Air ±8KV perf.Criteria B |
Pulse train anti-interference | IEC/EN61000-4-4 ±2KV perf.Criteria B |
Surge immunity | IEC/EN61000-4-5 ±2KV perf.Criteria B |
Voltage drop & short interruption immunity | IEC/EN61000-4-29 0%~70% perf.Criteria B |
Isolation voltage | Signal input, output, power: 1500VAC 1min <60V low voltage circuit: DC500V,1min |
Total weight | About 400g |
Cover material | The shell and panel frame PC/ABS (Flame Class UL94V-0) |
Panel material | PC |
Power failure memory | 10 years, times of writing: 1 million times |
Safety Standard | IEC61010-1 Overvoltage category Ⅱ,pollution level 2, levelⅡ(Enhanced insulation) |
Measuring signal specifications:
4. Dimention:
5. Connections:
6. Contact:
Sales: bassy shi
Cell phone: +86 13773069136
Email: bassy.shi@youjiazhineng.com
Contact Person: Ms. Julie
Tel: +86-180-2126-2273
Fax: 86-512-52843553